- 900mA single loop (digital communication) addressable fire alarm control panel
- Up to 32 G-One, GEKKO, OCTO+ and NODE+ panels can be networked
- Connection to the repeater panels via RS422, Fibre-Optic or TCP/IP
- 250 devices per loop (125 address limit)
- Up to 95 VULCAN 2 (addressable) ultra-low current base sounders (32 address limit) per loop.
- 32 individually programmable sounder addresses
- Full Self-Addressing device support
- 2 Fire output relays (change-over) and 1 Fault relay (NC)
- 2 Non-addressable (conventional) alarm outputs (individually programmable)
- High integrity loop communication and device monitoring
- 384 fully programmable network zones
- 512 fully programmable alarm (sounder) groups
- 512 I/O groups
- Event log (10,000 events)
- Compatible with ZEOS, GFE and Apollo™ digital analogue addressable protocols
- Compatible with all GFE manufactured digital addressable ancillary modules
- High resolution, high contrast backlit blue graphical LCD display (240 x 64 pixels)
- Programming by integrated tactile keypad or USB Loader PC software
- Multiple menu selectable language support
- 16 integrated programmable fire zone LED’s
- SMS and EMAIL notification by means of TCP IP-WEB interface
- Installer friendly automatic self-learn facility
- CPR Certified to EN54-2 and EN54-4