The DIGITUS® Smart PDU measures the electronic parameters per phase, per group and per output. The outputs can also be switched individually by remote. Definable thresholds with alarms increase the availability of connected users. The integrated communication card enables interconnection of up to 5 PDUs via one IP address as well as the remote monitoring and maintenance of all connected units. An integrated display shows all measured values and the PDU status. Additional external sensors (temperature, humidity, door contacts, smoke or water) can be connected to the communication card. The PDU can be installed without tools or permanently in DIGITUS® racks or other housing systems with appropriate mountings.
TECHNICAL DETAILS
Input monitoring: Current (A), voltage (V), energy (kWh), power (kW), power factor
Output monitoring per output: Current (A), energy (kWh), power (kW)
Individual switching of the outputs
User-defined sequential delay for switching outputs on/off
User-defined thresholds for voltage and current per phase, output or group
Comprehensive user-defined alarm management (remote and local)
2 sensor ports for the connection of external sensors (temperature, humidity, door contacts, smoke or water); expandable with an external sensor box
Daisy-chaining of up to five PDUs (including master device)
Internal storage of alarms and measured values (graphic display)
Firmware update of the PDU possible remotely or via USB
User management for up to 10 users
Remote connections: 10/100 Mbits Ethernet, serial RS485, USB
Protocols: HTTP(s), SSL, Telnet, TCP/IP, SNMP v1/v2/v3, DHCP, UDP, SSH, DNS, SMTP(s), NTP, Radius, Syslog, Modbus RTU
Encryption: TLS1.3
Input: Plug IEC60309 1ph/N/PE 6h, 230 V / 16 A
Output: Device sockets IEC60320 20 x C13 (max. 10 A per output), 4 x C19 (max. 16 A per output)
Cable: Cable cross section 2.5 mm², length: 3 m
Dimensions (mm, LxWxH): 1850 x 56 x 52
Temperature range (operation / storage): 0 °C to +45 °C/ -20 °C to +70 °C
Humidity range (operation / storage): 5% - 95% RH / 5 - 95% RH (non-condensing)
Maximum height above sea level (operation / storage): 0 - 3,000 m / 0 - 15,000 m
Approvals: CE conformity
Current: 16 A
Input Plug: IEC 60309 16A 1ph/N/PE 6h
Installation: Rack 0U
Metering: PDU Metering, Outlet Metering
Outlets: IEC 60320 C13, IEC 60320 C19
Phase: 1ph
Power: 3,6 kVA
Volts: 230 V